Amana Central air conditioner not cooling properly
When an Amana central air conditioner is not cooling properly, start with the main control board, which can prevent the condensing unit contactor from receiving 24 volts or keep the furnace blower motor from getting power. Next, check for an airflow problem: a clogged air filter or blower wheel can restrict air, cause the evaporator coil to freeze, and leave your central air not cooling or blowing warm air. A failed contactor can also keep the outdoor unit from receiving power, while a defective dual run capacitor may make the condenser fan motor noisy, overheated, or unable to run. If the coils are clean, airflow is strong, and the fan, compressor, and blower motor operate but the AC is still not cold, a refrigerant leak or restriction in the sealed system is likely. A relay board can also stop power from reaching the blower motor. Turn off power at the disconnect box and circuit breaker before inspecting components, and do not work on 240V wiring unless qualified. Refrigerant diagnosis or any sealed-system repair requires EPA 608 certification and a licensed HVAC technician. Enter your model number to find the exact replacement part for your Amana central air conditioner.
01 - Amana Central Air Conditioner Main Control Board
If the central air condensing unit contactor is not receiving 24 volts or power is not getting to the furnace blower motor, a possible cause is a defective furnace main control board. While this is not a common problem, if all other potentially faulty components are working properly, the main control board should be replaced.
Enter model number to search for the required part specific to your product
Proper air flow is critical for the central air conditioner to work properly. The evaporator needs proper air flow to keep the condensing water from freezing. If the air filter or blower wheel gets clogged, ice can start forming on the evaporator coils, eventually freezing them up and preventing proper air flow. It is recommended to replace the air filter at least every 6 months or sooner depending on the conditions. Refer to owner's manual for guidance. Avoid covering registers with furniture, rugs, or other items that will restrict the air flow.
Top Solution
03 - Amana Central Air Conditioner Contactor
The furnace control board sends a low voltage signal to the contactor. When the contactor receives the signal from the control board, it closes the circuit, sending voltage to the condensing unit components. If the contactor is defective, it will not provide voltage to the condensing unit. To determine if the contactor is at fault, use a multimeter to test the contactor for continuity. If the contactor does not have continuity, replace it.
04 - Amana Central Air Conditioner Dual Run Capacitor
If the dual run capacitor is defective, the fan motor might be noisy, overheat, or not run at all. To determine if the dual run capacitor has failed, inspect the capacitor. If the dual run capacitor is bulging or leaking, replace it.
If the unit has good air flow, the evaporator and condensing unit coils are clean, the fan and compressor are running, and the furnace blower is on, but there is still not enough cooling, it is likely there is a leak or restriction in the sealed system. Since diagnosing and repairing a sealed system takes specialized tools and knowledge, a qualified service technician should diagnosis and repair the unit.
Highly Likely
06 - Amana Central Air Conditioner Relay Board
A relay board is often used to control components of an a central air condidtioner. If the blower motor is not receiving power, the relay board is likely the cause. A defective relay board will need to be replaced.