If your Lennox central air conditioner won't turn off, a shorted contactor or a bad wall thermostat or thermostat wiring is the most likely cause, keeping a cooling signal on the yellow (Y) terminal even after the thermostat is set to Off. A shorted furnace control board or main control board can cause the same problem, though it is a less common cause, by continuing to send voltage to the outdoor condensing unit and making the air conditioner run constantly. A shorted control board or main control board can continuously send voltage to the outdoor condensing unit, making the air conditioner run constantly even when the thermostat is set to off. Next, check the wall thermostat or thermostat wiring. A stuck electrical contact between the common "C" and yellow "Y" thermostat wire terminals can keep signaling the contactor to run. A failed contactor is less common, but a shorted contactor can also provide continuous power to the condenser components. This central air won't turn off problem may be caused by a control board, thermostat, thermostat wire issue, or contactor. Enter your Lennox model number to find the exact replacement part for your specific central air conditioner. You can inspect the thermostat and control board for visible damage, but testing continuity and working around the contactor, condensing unit, or other 240-volt line-voltage components requires power to be disconnected and should be handled by a qualified HVAC technician if you are not trained to do so. No refrigerant handling is needed for these repairs.
01 - Lennox Central Air Conditioner Control Board
If the furnace control board has a short, it may be providing continuous voltage to the central air condensing unit preventing it from turning off. Inspect the control board for any damage and replace if necessary.
Enter model number to search for the required part specific to your product
02 - Lennox Central Air Conditioner Main Control Board
If the furnace's main control board has a short, it may be providing continuous voltage to the central air condensing unit preventing it from turning off. Inspect the control board for any damage and replace if necessary.
03 - Lennox Central Air Conditioner Wall Thermostat
The wall thermostat has electrical contacts that send signal voltage back to the control board and the condensing unit's contactor to run the central air system. If the contact that controls the contactor sticks closed, it will send continuous voltage to the contactor, causing the central air system to run continuously. To determine if the thermostat is defective, use a multi-meter to test it for continuity. If the wall thermostat shows continuity between the common (“C”) and yellow (“Y”) thermostat wire terminals when the thermostat is in the off position, the thermostat has failed and will need to be replaced.
04 - Lennox Central Air Conditioner Wifi Thermostat
The WiFi thermostat has electrical contacts that send signal voltage back to the control board and the condensing unit's contactor to run the central air system. If the contact that controls the contactor sticks closed, it will send continuous voltage to the contactor, causing the central air system to run continuously. To determine if the thermostat is defective, use a multi-meter to test it for continuity. If the WiFi thermostat shows continuity between the common (“C”) and yellow (“Y”) thermostat wire terminals when the thermostat is in the off position, the thermostat has failed and will need to be replaced.
The furnace control board sends a low voltage signal to the contactor. When the contactor receives the signal from the control board, it closes the circuit, sending voltage to the condensing unit components. If the contactor has shorted, it can send continuous voltage to the condensing unit's components resulting in the central air system not turning off. To determine if the contactor is at fault, use a multimeter to test the contactor for a short. If the contactor has shorted, replace it.